Air Handling Unit

Home Air Handling Unit

Air Handling Unit

Total 31 Air Handling Unit’s catering to different areas to maintain the Classification required and 01 APU for Coating machine for maintaining 0% RH.

RLAF and LAF is installed at RM Dispensing, sampling, Microbiology laboratory etc.

Intake of Fresh Air in AHU System: 10 Micron @ 10%.

Air Filtration: Up to 0.3 Micron terminal HEPA Filters in critical areas.

Environmental Exhaust Air: through 0.3 Micron for ACD systems @ 10%.

Minimum air changes are considered for all Clean areas as follows: -

  • For EUGMP Grade-B - Not less than 90 air changes per hour.
  • For EUGMP Grade-C - Not less than 60 air changes per hour.
  • For EUGMP Grade-D - Not less than 30 air changes per hour.

Temperature: NMT 25°C

Relative Humidity : NMT 25% in Core areas (as per product requirement) (“Dry” Storage condition) and NMT 55% as per need base.

AHUs Installed basically to protect Environmental contamination, crosscontamination, personal comfort.

Schematic Layout Of HVAC System

First floor layout