Air Handling Unit
Total 31 Air Handling Unit’s catering to different areas to maintain the
Classification required and 01 APU for Coating machine for maintaining 0% RH.
RLAF and LAF is installed at RM Dispensing, sampling, Microbiology laboratory etc.
Intake of Fresh Air in AHU System: 10 Micron @ 10%.
Air Filtration: Up to 0.3 Micron terminal HEPA Filters in critical areas.
Environmental Exhaust Air: through 0.3 Micron for ACD systems @ 10%.
Minimum air changes are considered for all Clean areas as follows: -
- For EUGMP Grade-B - Not less than 90 air changes per hour.
- For EUGMP Grade-C - Not less than 60 air changes per hour.
- For EUGMP Grade-D - Not less than 30 air changes per hour.
Temperature: NMT 25°C
Relative Humidity : NMT 25% in Core areas (as per product requirement) (“Dry”
Storage condition) and NMT 55% as per need base.
AHUs Installed basically to protect Environmental contamination, crosscontamination, personal comfort.